🌊 LogUp β€” from the box to live data

Commissioning the Lacroix SOFREL LogUp on ScadaBOSS. Field-proven sequence β€” a typical site is online in under an hour. Have your wiring drawing from the quote package handy.

1

Bench first β€” wire the sensors

Terminate per your ScadaBOSS wiring drawing: 4–20 mA transmitters on AI1/AI2 (2-wire, loop-powered β€” the LogUp energizes the loop only at sample time), dry contacts on DI1/DI2 (no voltage β€” floats, pump-fail relays, hatch switches).

⚠ Verify conductor colors against the legend printed on the supplied cable before terminating. Surge protection on anything leaving the structure; gas-tight splices in wet wells.
2

Pair the phone app

Install My SOFREL LogUp (Google Play / App Store). Wake the logger and connect over Bluetooth β€” the app shows live readings from your sensors immediately, no cloud round-trip. Confirm your 4–20 signal moves and scales correctly right here on the bench.

βœ“ Checkpoint: live value in the app tracks your sensor.
3

Configure in LX CONNECT

In the Lacroix LX CONNECT portal (Devices β†’ your unit β†’ Configuration): name the channels, scale AI1 to engineering units, set measurement periodicity (5–15 min logging) and transmission periodicity (daily is the battery sweet spot).

Most important: set the device-side alarm thresholds (high level, low pressure…). A crossed threshold makes the LogUp call in immediately instead of waiting for the daily sync β€” that's your alarm path.

The Autonomy figure recalculates as you change periodicity β€” check it before applying. Daily reporting + alarm-triggered sends β‰ˆ 9-year battery.
4

Trigger a send β€” confirm the cloud

From the app, trigger a communication. Within a minute the device shows a fresh Last connection in LX CONNECT with your channel data.

βœ“ Checkpoint: today's timestamp on the device in LX CONNECT.
5

Add it to ScadaBOSS

On Monitoring β†’ + Add Device, pick your application β€” Lacroix LX β€” Lift Station, Water Tank or Booster β€” and paste the device UID from LX CONNECT (Devices β†’ Description). Once approved, ScadaBOSS pulls from the Lacroix cloud automatically: no credentials touch the logger, nothing else to configure.

βœ“ Checkpoint: your site appears on πŸ“Ÿ Fleet within 5 minutes of approval, with the automatic offline watchdog already armed.
6

Cloud alarms & notifications

On πŸ”” Alarming: your device's cloud-alarm toggle is already ON. Pick a tag, set Hi/Lo/rate-of-change setpoints against the live statistics shown, choose email, Pushover or both, and press Send test alarm to prove delivery to your phone.

Put a Lo on Battery_DaysLeft @ 180 and a Lo on Reception_dBm @ βˆ’105 on every unit β€” battery replacement and antenna problems announce themselves months ahead.

7

Install in the field

Mount, connect the real sensors, then trigger one more app send from the final position and check Reception_dBm on the site page β€” better than βˆ’95 dBm is comfortable; worse, move the unit topside or fit a remote antenna. Finish with a real alarm test: lift the float or crack the tap, and watch the email + push arrive.

βœ“ Done β€” daily data, instant alarms, ~9 years on the battery.